The following are EH&IS recommended lighting levels using Illuminating Engineering Society (IES) guidelines:

Classrooms

50 to 100 foot-candles, depending upon need. Recommended light level is 70 foot-candles as measured on top of student desks.

Offices

50 to 150 foot-candles, depending upon need. Recommended light level is 70 foot-candles as measured on the top of desks. Higher levels of light needed because of more difficult work should be achieved by supplementary sources such as desk lamps.

Hallways, stairs, and public assembly areas

10 foot-candles is the recommended light level for all these high traffic areas. No part of these public areas should have a light level lower than 2 foot-candles.

Building entrances

5 foot-candles is the recommended light level for the outside area of building entrances.

Outdoor walkways

One foot-candle is the recommended light level for all parts of outdoor walkways and other public foot traffic areas.

Parking Surface Lots

One foot-candle is the recommended light level for all parking lot areas.

Parking Structure

Five foot-candle is the recommended light level

Revised: 9/23/2004 TW